| Report on Code Compliance - Quick Pole Line Design Software | Yes | ||||||||||
| Summary by Section | Yes | Partial | No | N/A | Total Clauses | No | |||||
| General Requirements 200-239 | 10 | 5 | 22 | 22 | 59 | Partial | |||||
| Grades of construction 240 | 0 | 3 | 0 | 1 | 4 | N/A | |||||
| Assumed Loads 250 | 9 | 1 | 0 | 1 | 11 | ||||||
| Strength 260 | 9 | 2 | 6 | 1 | 18 | ||||||
| Other | 0 | 0 | 3 | 0 | 3 | ||||||
| Total | 28 | 11 | 31 | 25 | 95 | ||||||
| 40% | 16% | 44% | |||||||||
| C2-2017 National Electric Safety Code | Compliant ? | Notes / Proof | 70 | ||||||||
| 200 Purpose | N/A | 0 | 0 | 0 | 1 | ||||||
| 201 Scope | N/A | 0 | 0 | 0 | 1 | ||||||
| 202 Application of rules | N/A | 0 | 0 | 0 | 1 | ||||||
| 210 Referenced sections | N/A | 0 | 0 | 0 | 1 | ||||||
| 212 Induced Voltages | N/A | 0 | 0 | 0 | 1 | ||||||
| 213 Accessibility | N/A | 0 | 0 | 0 | 1 | ||||||
| 214 Inspections and tests of lines and equipment | N/A | 0 | 0 | 0 | 1 | ||||||
| 215 Grounding of circuits, supporting structures and equipment | No | Grounding design or grounding of items is not evaluated | 0 | 0 | 1 | 0 | |||||
| 216 Arrangement of switches | N/A | 0 | 0 | 0 | 1 | ||||||
| 217 General | N/A | 0 | 0 | 0 | 1 | ||||||
| 218 Vegetation Management | N/A | 0 | 0 | 0 | 1 | ||||||
| 220 Relative Levels | N/A | 0 | 0 | 0 | 1 | ||||||
| 221 Avoidance of conflict | N/A | 0 | 0 | 0 | 1 | ||||||
| 222 Joint use of structures | N/A | 0 | 0 | 0 | 1 | ||||||
| 223 Communication protective requirements | N/A | 0 | 0 | 0 | 1 | ||||||
| 224.A Communication circuits located within the supply space | No | These cables will attract the same evaluation as other communication cables at this time | 0 | 0 | 1 | 0 | |||||
| 224.B Supply circuits used exclusively for communication circuits | N/A | 0 | 0 | 0 | 1 | ||||||
| 225 Electric railway construction | No | 0 | 0 | 1 | 0 | ||||||
| 230.A Clearances - General | N/A | 0 | 0 | 0 | 1 | ||||||
| 230.B Ice and wind loading for clearances | Yes | Except - Spaced aerial cable and cables in rings not currently supported for the addition of the constant load | 1 | 0 | 0 | 0 | |||||
| 230.C Supply Cables supported by grounded neutral/messenger | Yes | 1 | 0 | 0 | 0 | ||||||
| 230.D Covered conductors | Yes | 1 | 0 | 0 | 0 | ||||||
| 230.E Neutral Conductors | Yes | 1 | 0 | 0 | 0 | ||||||
| 230.F Fibre-optic cable | Partial | fibre-optic supply cables are treated in Quick Pole the same as regular communication cables | 0 | 1 | 0 | 0 | |||||
| 230.G Alternating and direct-current circuits | Yes | 1 | 0 | 0 | 0 | ||||||
| 230.H Constant-current circuits | Yes | 1 | 0 | 0 | 0 | ||||||
| 230.I Maintenance of clearances | N/A | 0 | 0 | 0 | 1 | ||||||
| 231 Clearances of supporting structures from other objects | No | 0 | 0 | 1 | 0 | ||||||
| 232 Vertical clearance of wires… | N/A | 0 | 0 | 0 | 1 | ||||||
| 232.A Application | Yes | Except the clearance test for trolley wires at 15C | 1 | 0 | 0 | 0 | |||||
| 232.B Clearances of wires… | Partial | Except clearances of wires over boat ramps and fixed live parts as per Table 232-2. Also supply service drops to residential buildings of lower than 750 volts are not specially recognized in Quick Pole and so will require clearance for 750 volts. Communication service drops not specially recognized when crossing residential driveways, thus requiring communication cable clearances. Drip loops of supply service wires are not input into Quick Pole for clearance to ground tests. | 0 | 1 | 0 | 0 | |||||
| 232.C Voltages 22KV - 98KV | Yes | Except high elevation adjustment | 1 | 0 | 0 | 0 | |||||
| 232.D Greater voltages | Yes | Except high elevation adjustment | 1 | 0 | 0 | 0 | |||||
| 233 Clearances between wires… | No | Horizontal swing values available in reports, but automatic separation tests not implemented. | 0 | 0 | 1 | 0 | |||||
| 234 Clearances of wires… from buildings, … | No | Same as 233 | 0 | 0 | 1 | 0 | |||||
| 235 Clearances for wires… on the same supporting structure | N/A | 0 | 0 | 0 | 1 | ||||||
| 235.A Application of rule | N/A | 0 | 0 | 0 | 1 | ||||||
| 235.B Horizontal clearance between line conductors | No | 0 | 0 | 1 | 0 | ||||||
| 235.C Vertical separations | No | 0 | 0 | 1 | 0 | ||||||
| 235.D Diagonal separations | No | 0 | 0 | 1 | 0 | ||||||
| 235.E Clearances in any direction | No | 0 | 0 | 1 | 0 | ||||||
| 235.F Clearances between supply circuits on the same support arm | No | 0 | 0 | 1 | 0 | ||||||
| 235.G Conductor spacing on vertical racks | N/A | 0 | 0 | 0 | 1 | ||||||
| 235.H Separation between communication conductors, cables… | No | 0 | 0 | 1 | 0 | ||||||
| 235.I Clearances for Antenna | No | 0 | 0 | 1 | 0 | ||||||
| 236 Climbing space | No | 0 | 0 | 1 | 0 | ||||||
| 237 Working space | No | 0 | 0 | 1 | 0 | ||||||
| 238 Vertical clearance between communications and supply on the same structure | Partial | Luminaires, traffic signals or trolley conductors are assumed not effectively grounded and require 1.0m vertical clearance above communications | 0 | 1 | 0 | 0 | |||||
| 239 Clearance of vertical and lateral facilities from other facilities on the same structure | N/A | 0 | 0 | 0 | 1 | ||||||
| 239.A General | No | Facilities in conduit are not tracked in Quick Pole. | 0 | 0 | 1 | 0 | |||||
| 239.B Location relative to climbing space | No | Climbing space tests not performed | 0 | 0 | 1 | 0 | |||||
| 239.C Conductors not in conduit | No | 0 | 0 | 1 | 0 | ||||||
| 239.D Guarding and protection near ground | No | 0 | 0 | 1 | 0 | ||||||
| 239.E Vertical and lateral Supply conductor requirements | No | 0 | 0 | 1 | 0 | ||||||
| 239.F Vertical and Lateral Communication requirements | Partial | Clearances from supply and communication is enforced. | 0 | 1 | 0 | 0 | |||||
| 239.G Vertical supply passing through communication space | Yes | Use of conduit and luminaire equipment required for these tests. Exception: Clearance from through-bolts not supported. | 1 | 0 | 0 | 0 | |||||
| 239.H Communications passing through Supply space | No | 0 | 0 | 1 | 0 | ||||||
| 239.I Operating rods | No | Operating rods are not assessed by Quick Pole | 0 | 0 | 1 | 0 | |||||
| 239.J Stand-off brackets | Partial | Stand-off brackets can be added as equipment, but clearance tests as per Table 239-1 are not performed | 0 | 1 | 0 | 0 | |||||
| 240 Grades of Construction - General | N/A | 0 | 0 | 0 | 1 | ||||||
| 241 Application of grades of construction to different situations | Partial | User determines and selects the proper grade | 0 | 1 | 0 | 0 | |||||
| 242 Grades of construction for conductors | Partial | User determines and selects the proper grade | 0 | 1 | 0 | 0 | |||||
| 243 Grades of construction for line supports | Partial | User determines and selects the proper grade | 0 | 1 | 0 | 0 | |||||
| 250.A General loading requirements and maps - General | Yes | 1 | 0 | 0 | 0 | ||||||
| 250.B Combined ice and wind loading | Yes | 1 | 0 | 0 | 0 | ||||||
| 250.C Extreme wind loading | Yes | User needs to enter extreme wind speed and corresponding temperature. It is assumed that structure is exposed to extreme wind; user can turn off if appropriate. | 1 | 0 | 0 | 0 | |||||
| 250.D Extreme ice with concurrent wind | Yes | User needs to enter ice thickness and wind values required. For Grade C, user could multiply ice thickness by a factor of 0.8 | 1 | 0 | 0 | 0 | |||||
| 251 Conductor loading | Yes | 1 | 0 | 0 | 0 | ||||||
| 252 Loads on line supports | N/A | 0 | 0 | 0 | 1 | ||||||
| 252.A Assumed vertical loads | Yes | 1 | 0 | 0 | 0 | ||||||
| 252.B Assumed transverse loads | Yes | 1 | 0 | 0 | 0 | ||||||
| 252.C Assumed longitudinal loads | Partial | A Line Grade change locations (252C.1), the user needs to compute value and add as a Point Load to the structure. Tension limits for small communication conductors are not enforced. | 0 | 1 | 0 | 0 | |||||
| 252.D Simultaneous application of loads | Yes | 1 | 0 | 0 | 0 | ||||||
| 253 Load factors for structures… | Yes | 1 | 0 | 0 | 0 | ||||||
| 260 Strength requirements | Yes | 1 | 0 | 0 | 0 | ||||||
| 261 Grades B and C construction | N/A | 0 | 0 | 0 | 1 | ||||||
| 261.A Supporting structures | Yes | Except longitudinal requirements. | 1 | 0 | 0 | 0 | |||||
| 261.B Strength of foundations, settings and guy anchors | Yes | 1 | 0 | 0 | 0 | ||||||
| 261.C Strength of guys | Yes | 1 | 0 | 0 | 0 | ||||||
| 261.D Crossarms and braces | No | 0 | 0 | 1 | 0 | ||||||
| 261.E Insulators | No | 0 | 0 | 1 | 0 | ||||||
| 261.F Strength of pin-type or similar construction | No | 0 | 0 | 1 | 0 | ||||||
| 261.G Armless construction | Yes | 1 | 0 | 0 | 0 | ||||||
| 261.H Open supply conductors and overhead sheild wires | Partial | Aeolian vibration, splices and size of trolley contact wires not considered | 0 | 1 | 0 | 0 | |||||
| 261.I Supply cable messengers | Yes | 1 | 0 | 0 | 0 | ||||||
| 261.J Open-wire Communication conductors | Yes | 1 | 0 | 0 | 0 | ||||||
| 261.K Communication cables and messengers | Yes | 1 | 0 | 0 | 0 | ||||||
| 261.L Paired metallic communication conductors | No | 0 | 0 | 1 | 0 | ||||||
| 261.M Support and attachment hardware | No | 0 | 0 | 1 | 0 | ||||||
| 261.N Climbing and working steps | No | 0 | 0 | 1 | 0 | ||||||
| 263 Grade N construction | Partial | Minimum conductor sizes not tested. | 0 | 1 | 0 | 0 | |||||
| 264 Guying and bracing | Yes | Guy load determined through Finite Element Analysis as part of structure analysis | 1 | 0 | 0 | 0 | |||||
| 270 - 277 Insulator requirements | No | 0 | 0 | 1 | 0 | ||||||
| 278 Aerial cable systems | No | 0 | 0 | 1 | 0 | ||||||
| 279 Guy and span insulators | No | 0 | 0 | 1 | 0 | ||||||