Report on Code Compliance - Quick Pole Line Design Software Yes
Summary by Section Yes Partial No N/A Total Clauses No
General Requirements 200-239 10 5 22 22 59 Partial
Grades of construction 240 0 3 0 1 4 N/A
Assumed Loads 250 9 1 0 1 11
Strength 260 9 2 6 1 18
Other 0 0 3 0 3
Total 28 11 31 25 95
40% 16% 44%
C2-2017 National Electric Safety Code Compliant ? Notes / Proof 70
200 Purpose N/A 0 0 0 1
201 Scope N/A 0 0 0 1
202 Application of rules N/A 0 0 0 1
210 Referenced sections N/A 0 0 0 1
212 Induced Voltages N/A 0 0 0 1
213 Accessibility N/A 0 0 0 1
214 Inspections and tests of lines and equipment N/A 0 0 0 1
215 Grounding of circuits, supporting structures and equipment No Grounding design or grounding of items is not evaluated 0 0 1 0
216 Arrangement of switches N/A 0 0 0 1
217 General N/A 0 0 0 1
218 Vegetation Management N/A 0 0 0 1
220 Relative Levels N/A 0 0 0 1
221 Avoidance of conflict N/A 0 0 0 1
222 Joint use of structures N/A 0 0 0 1
223 Communication protective requirements N/A 0 0 0 1
224.A Communication circuits located within the supply space No These cables will attract the same evaluation as other communication cables at this time 0 0 1 0
224.B Supply circuits used exclusively for communication circuits N/A 0 0 0 1
225 Electric railway construction No 0 0 1 0
230.A Clearances - General N/A 0 0 0 1
230.B Ice and wind loading for clearances Yes Except - Spaced aerial cable and cables in rings not currently supported for the addition of the constant load 1 0 0 0
230.C Supply Cables supported by grounded neutral/messenger Yes 1 0 0 0
230.D Covered conductors Yes 1 0 0 0
230.E Neutral Conductors Yes 1 0 0 0
230.F Fibre-optic cable Partial fibre-optic supply cables are treated in Quick Pole the same as regular communication cables 0 1 0 0
230.G Alternating and direct-current circuits Yes 1 0 0 0
230.H Constant-current circuits Yes 1 0 0 0
230.I Maintenance of clearances N/A 0 0 0 1
231 Clearances of supporting structures from other objects No 0 0 1 0
232 Vertical clearance of wires… N/A 0 0 0 1
232.A Application Yes Except the clearance test for trolley wires at 15C 1 0 0 0
232.B Clearances of wires… Partial Except clearances of wires over boat ramps and fixed live parts as per  Table 232-2. Also supply service drops to residential buildings of lower than 750 volts are not specially recognized in Quick Pole and so will require clearance for 750 volts. Communication service drops not specially recognized when crossing residential driveways, thus requiring communication cable clearances. Drip loops of supply service wires are not input into Quick Pole for clearance to ground tests.  0 1 0 0
232.C Voltages 22KV - 98KV Yes Except high elevation adjustment 1 0 0 0
232.D Greater voltages Yes Except high elevation adjustment 1 0 0 0
233 Clearances between wires… No Horizontal swing values available in reports, but automatic separation tests not implemented. 0 0 1 0
234 Clearances of wires… from buildings, … No Same as 233 0 0 1 0
235 Clearances for wires… on the same supporting structure N/A 0 0 0 1
235.A Application of rule N/A 0 0 0 1
235.B Horizontal clearance between line conductors No 0 0 1 0
235.C Vertical separations No 0 0 1 0
235.D Diagonal separations No 0 0 1 0
235.E Clearances in any direction No 0 0 1 0
235.F Clearances between supply circuits on the same support arm No 0 0 1 0
235.G Conductor spacing on vertical racks N/A 0 0 0 1
235.H Separation between communication conductors, cables… No 0 0 1 0
235.I Clearances for Antenna No 0 0 1 0
236 Climbing space No 0 0 1 0
237 Working space No 0 0 1 0
238 Vertical clearance between communications and supply on the same structure Partial Luminaires, traffic signals or trolley conductors are assumed not effectively grounded and require 1.0m vertical clearance above communications 0 1 0 0
239 Clearance of vertical and lateral facilities from other facilities on the same structure N/A 0 0 0 1
239.A General No Facilities in conduit are not tracked in Quick Pole. 0 0 1 0
239.B Location relative to climbing space No Climbing space tests not performed 0 0 1 0
239.C Conductors not in conduit No 0 0 1 0
239.D Guarding and protection near ground No 0 0 1 0
239.E Vertical and lateral Supply conductor requirements No 0 0 1 0
239.F Vertical and Lateral Communication requirements Partial Clearances from supply and communication is enforced. 0 1 0 0
239.G Vertical supply passing through communication space Yes Use of conduit and luminaire equipment required for these tests. Exception: Clearance from through-bolts not supported. 1 0 0 0
239.H Communications passing through Supply space No 0 0 1 0
239.I Operating rods No Operating rods are not assessed by Quick Pole 0 0 1 0
239.J Stand-off brackets Partial Stand-off brackets can be added as equipment, but clearance tests as per Table 239-1 are not performed 0 1 0 0
240 Grades of Construction - General N/A 0 0 0 1
241 Application of grades of construction to different situations Partial User determines and selects the proper grade 0 1 0 0
242 Grades of construction for conductors Partial User determines and selects the proper grade 0 1 0 0
243 Grades of construction for line supports Partial User determines and selects the proper grade 0 1 0 0
250.A General loading requirements and maps - General Yes 1 0 0 0
250.B Combined ice and wind loading Yes 1 0 0 0
250.C Extreme wind loading Yes User needs to enter extreme wind speed and corresponding temperature. It is assumed that structure is exposed to extreme wind; user can turn off if appropriate. 1 0 0 0
250.D Extreme ice with concurrent wind Yes User needs to enter ice thickness and wind values required. For Grade C, user could multiply ice thickness by a factor of 0.8 1 0 0 0
251 Conductor loading Yes 1 0 0 0
252 Loads on line supports N/A 0 0 0 1
252.A Assumed vertical loads Yes 1 0 0 0
252.B Assumed transverse loads Yes 1 0 0 0
252.C Assumed longitudinal loads Partial A Line Grade change locations (252C.1), the user needs to compute value and add as a Point Load to the structure. Tension limits for small communication conductors are not enforced. 0 1 0 0
252.D Simultaneous application of loads Yes 1 0 0 0
253 Load factors for structures… Yes 1 0 0 0
260 Strength requirements Yes 1 0 0 0
261 Grades B and C construction N/A 0 0 0 1
261.A Supporting structures Yes Except longitudinal requirements. 1 0 0 0
261.B Strength of foundations, settings and guy anchors Yes 1 0 0 0
261.C Strength of guys Yes 1 0 0 0
261.D Crossarms and braces No 0 0 1 0
261.E Insulators No 0 0 1 0
261.F Strength of pin-type or similar construction No 0 0 1 0
261.G Armless construction Yes 1 0 0 0
261.H Open supply conductors and overhead sheild wires Partial Aeolian vibration, splices and size of trolley contact wires not considered 0 1 0 0
261.I Supply cable messengers Yes 1 0 0 0
261.J Open-wire Communication conductors Yes 1 0 0 0
261.K Communication cables and messengers Yes 1 0 0 0
261.L Paired metallic communication conductors No 0 0 1 0
261.M Support and attachment hardware No 0 0 1 0
261.N Climbing and working steps No 0 0 1 0
263 Grade N construction Partial Minimum conductor sizes not tested. 0 1 0 0
264 Guying and bracing Yes Guy load determined through Finite Element Analysis as part of structure analysis 1 0 0 0
270 - 277 Insulator requirements No 0 0 1 0
278 Aerial cable systems No 0 0 1 0
279 Guy and span insulators No 0 0 1 0